INOR · Alarm Units
Download INOR catalog (PDF)
INOR SR336
Alarm Unit with RTD Input and Double Relay Outputs
Programmable alarm unit for temperature monitoring with RTD sensors in 2-wire connection in process industry; two synchronously switching relays offer MIN/MAX alarm functions in open- or closed-circuit operation; front LEDs show alarm state and power supply
Switching point and hysteresis set by front potentiometers; relay functions by front DIP switches
High 4-port isolation; protective separation per DIN EN 61140 via reinforced insulation per DIN EN 61010
Technical specification
- Model
- INOR SR336
- Input
- RTD / resistance 0…3 kΩ
- Output
- 2 × relay, 250 VAC / 6 A
- Accuracy
- 0.2% of span
- Power supply
- 24 VDC
- Isolation
- 4000 VAC
- Mounting
- DIN rail
Specifications
- Input
- any RTD or resistance signal, 2-wire; ranges 0-300 Ω or 0-3000 Ω
- Outputs
- two synchronous SPDT relays, monostable for safe tripping on power failure, up to 6 A
- Power supply
- 24 V DC
- Mounting
- standard 35 mm DIN rail
Can't find an exact match?
Tell us your temperature range, mounting and dimensions and our engineers will design it for you.